Codmetel: HV000570

Multifunction tester for electric safety measurements and power quality analysis on single-phase and three-phase installations

In a single device, all functions of the most advanced systems for safety testing; power analyses, THREE-PHASE or SINGLE-PHASE (voltages, currents, powers, power factor, energies, etc.), voltage/ current harmonic analysis (up to the 49th) and an capturing of voltage anomalies (dips, peaks); continuity test with test current 10A.

The device has a whole variety of functions and can be used with external feelers for measuring environmental parameters such as temperature/ humidity of air, illuminance (Lux) further to measuring leakage currents, Loop/Line impedance and calculating the assumed shortcircuit current with high resolution (0.1mOhm) in TN systems with the use of the optional accessory IMP57. Cutting-edge management of measurement with indication, at the end of each safety test, of compliance or non-compliance with requirements with simple symbols OK or NOT OK.

Functions
Continuity of protective conductors with 200mA / 10A 200mA/10A
Internal memory capacity 2MB
Indicative memory duration (in days @ PI=10min @ max number of parameters) 32 days
Recording with selectable integration period 5s-60m
Max number of simultaneously selectable parameters 64
Provided PC interface with software for Windows Optical / USB
Active, reactive, apparent power/energy and DC power  
Saving instant sampled values  
AC/DC voltage and current in single-phase/three-phase systems  
Voltage and current harmonics up to the 49th with THD  
Insulation with voltage 50, 100, 250, 500, 1000VDC  
Earth resistance by voltammetric method  
Summary table of main electric parameters  
Voltage/current vector diagram  
Voltage/current waveforms  
Tripping time and current of RCDs type A, AC Standard, Selective  
Cosphi, Power Factor  
Tables or histograms of Harmonics and THD%  
Indicative memory duration (@ PI=10min @ max numb parameters)  
Indication of recording duration  
Guidelines
  • CE MARK
  • CEI 64-8 612.6.2
  • CEI 64-8
  • CEI 64-8 612.3 .4 .5
  • CEI 64-8 612.6.1
  • CEI 64-8 612.6.3
  • CEI 64-8/7
  • EMC 2004/108/CE Directive
  • LVD 2006/95/CE Directive
  • DPR 462 del 22/10/2001
  • EN 61008
  • IEC/EN 61010-1
  • IEC/EN61557-1
  • IEC/EN61557-2
  • IEC/EN61557-3
  • IEC/EN61557-4
  • IEC/EN61557-5
  • IEC/EN61557-6
  • IEC/EN61557-7
  • VDE 0100
  • CEI 64-8 612.2
  • EMC: IEC/EN61326
  • None
Picture

STANDARD ACCESSORIES

OPTIONAL ACCESSORIES